Making them useful especially for field testing where transport and space can be issues.
Vlf cable test.
Vlf testing uses very low frequencies as part of an ac cable maintenance routine.
Vlf systems are advantageous in that they can be manufactured to be small and lightweight.
Vlf testers are smaller and more practical than ac testers but output the same amount of power as a 50 hz mains device.
Vlf cable testing very low frequency is a technique for testing of medium and high voltage mv and hv cables.
The device under test must withstand a vlf very low frequency ac voltage for a preset testing time without flashover.
The hva28td vlf high voltage test set is an ultra compact lightweight 0 1 hz vlf cable tester with integrated tan delta diagnostics with monitored withstand test mwt testing and diagnostics in compliance with ieee400 smallest vlf td unit available.
Unlike with dc voltage testing very low frequency is not destructive to good insulation and does not lead to premature failures.
The hv test lead outside shield conductor is connected to the concentric neutral ground point of the cable under test.
This combination of size and power makes very low frequency cable testing perfect for testing longer sections of cable and apparatus.
Vlf cable testing is the cutting edge technology for proof testing of fully operating medium voltage cables and the detection of faulty ones.
Vlf testing uses very low frequencies as part of an ac cable maintenance routine.
In the first step a go no go statement is sufficient.
The other phases are grounded.
During the test cables are subjected to a test voltage significantly higher than what they experience during normal operating conditions.
Vlf testers are smaller and more practical than ac testers but output the same amount of power as a 50 hz mains device.
Vlf ac test voltages with cosinerectangular and the sinusoidal wave shapes are most commonly used.
The vlf test instrument should be solidly grounded before connecting up any cables.
Vlf testing can be classified as a withstand or diagnostic test meaning it may be performed as a proof test for acceptance or as a maintenance test for assessing the condition of cable.
Vlf ac voltage testing methods utilize ac signals at frequencies in the range of 0 01 hz to 1 hz.
The main conductor of the hv test lead is then connected to the conductor of the cable under test.
The most commonly used commercially available vlf ac voltage test frequency is 0 1 hz.
This kind of test is suited for testing high capacitance loads such.